
Parametr Value Description Default Exam.1
Exam.2
6 z
Acoustic signalling
3 and 9 3 and 9
3 and 9
In default the unit produces acoustic signals. It can occasionally cause a problem
of incorrect detection of tones by PBX. By changing parameter „z“ you can switch
off this acoustic signalization. The values are:
z=0 – all signalling is switched off
z=1 – pick up and hang up tones are active only
z=2 – other tones active only
(except pick up and hang up)
z=3 – all tones are active
– (
default)
It is possible to generate an audible signal (only in mode m=1) to alert visitors
that the door is unlocked so that they can enter. This is especially useful when
using a DC power source, as lock release may be silent.
z=8 – signalling is active
z=9 – signalling is unactive
Parameter
Value Description Default Exam.1
Exam.2
6* t
Delay of line connection
(Siemens PBX)
1 1 1
Setes a delay for line pick-up (OFF HOOK) for new PBX types (particularly
Siemens):
t=1 – standard operation
t=0 – delayed start
5.8 Overview of Parameters
Parameter
Value Description Default Exam.1 Exam.2
1 t nn… No. nn under button t
- - -
2 t nn… No. nn under button t
- - -
31 r
Relay mode
1 1 2
32 hhhhhh
External access code in
DAY + NIGHT mode
- 2211 1324
33 hhhhhh
External access code in
DAY mode
- 2211 2211
34 hhhhhh
External access code in
NIGHT mode
- 1122 1122
35 aa
Internal access code
1 impulse
55 55 55
Komentarze do niniejszej Instrukcji